69
MTIU-09HWFN1-M, MTIU-12HWFN1-M, MTIU-18HWFN1-M, MTIU-24HWFN1-M
A. Micro-switch SW1 is for selection of indoor fan stop temperature (TEL0) when it is in anti-cold wind
action in heating mode.
Range: 24
o
C, 15
o
C, 8
o
C, according to EEROM setting (reserved for special customizing).
T2
Setting fan speed
H
M+
M
L
Super slow
Fan off
TEL0+23- TE1
TEL0+21- TE1
TEL0+19- TE1
TEL0+17- TE1
TEL0+15- TE1
TEL0+13- TE1
TEL0+18- TE1
TEL0+16- TE1
TEL0+14- TE1
TEL0+12- TE1
TEL0+10- TE1
TEL0
B. Micro-switch SW3 is for selection of auto-restart function.
Range: Active, inactive
C.Micro-switch SW6 is for selection of temperature compensation in heating mode. This helps to reduce
the real temperature difference between ceiling and floor so that the unit could run properly. If the height