Specifications – Cooling and heating
Model MCCU-7HN2 MCCU-10HN2 MCCU-14HN2 MCCU-16HN2
Power supply 220-240V/1N/50Hz 380V/3N/50Hz 380V/3N/50Hz 380V/3N/50Hz
Ambient temp. range -10~45 -10~45 -10~45 -10~45
Cooling
Capacity W 7000 10000 14000 16000
Rated input W 3133 4333 4956 6033
Max. input W 3500 5800 6400 7400
EER - 2.23 2.31 2.83 2.65
Rated current A 13.3 6.73 8.92 10
Max. current A 18.7 10.4 11.5 13.2
Heating
Capacity W 7600 12000 15000 19000
Input W 3333 4610 5272 6418
COP - 2.28 2.60 2.85 2.96
Rated current A 10.69 7.3 8.28 10.55
Compressor
Model - PG480X3CS-4MU1 C-SBN303H8A ZR61KCE-TFD-522 C-SBN453H8A
Type - Rotary Scroll Scroll Scroll
Brand - Toshiba Sanyo Copeland Sanyo
Capacity W 8750 11850 14010 16500
Input W 2820 3900 4460 5430
Oil volume ml 1100 1700 1870 1700
Fan motor
Model - YDK53-6H YDK250-6D YDK250-6D YDK65-6F-1(×2)
Type - AC AC AC AC
Input W 155 296 296 171
Rated current A 0.73 1.38 1.38 0.78
Speed r/min 805 740 740 825
Outdoor coil
Number of rows - 2 2 2 2
Fin spacing mm 1.7 1.7 1.7 1.6
Fin type - Hydrophilic aluminum
Tube size mm Ф9.52 Ф9.52 Ф9.52 Ф7.94
Tube type - Inner-grooved
Coil (Lx H) mm 758×813 845×914 845×914 837×1100
Performance
Air flow volume m
3
/h 4000 5000 5000 6000
Noise level dB(A) 47 49 50 52
Refrigerant
Type - R407C R407C R407C R407C
Charge volume g 2300 2500 3100 4200
Piping
diameter
Liquid side mm Φ9.53 Φ12.7 Φ12.7 Φ9.53
Gas side mm Φ15.9 Φ19 Φ19 Φ19
Max. pipe length m 20 25 25 30
Max. high drop m 10 10 10 15
Unit dimension (W×H×D) mm 895×862×313 990×966×354 990×966×354 900×1167×340
Packing dimension (W×H×D) mm 1043×915×395 1120×1100×435 1120×1100×435 1032×1307×443
Net/ gross weight kg 64/66 96/106 90/96 104/112
Shipping Qty (20'/40'/40'HQ) pcs. 62/126/128 50/106/108 50/106/108 27/57/112
Notes:
1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent refrigerant piping: 7.5m (horizontal)
2. Nominal heating capacities are based on the following conditions:
Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal)