EasyManua.ls Logo

Midea MDV-V120W/DRN1

Midea MDV-V120W/DRN1
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MCAC-VTSM-2016-10 R410A All DC Inverter Mini VRF
Installation 61
Table 2: Indoor unit main pipes selection (L1~L5)
Total capacity of
downstream indoor units
(kW)
Main pipe size(mm)
Branch Pipe
Air pipe
Liquid pipe
A16.6
Φ15.9
Φ9.5
FQZHN-01C
16.6≤A23
Φ19.1
Φ9.5
FQZHN-01C
Table 3: Main pipes selection (L1)
Total capacity of
outdoor units
(kW)
When the equivalent length of all liquid and air
pipes < 90m
When the equivalent length of all liquid and air
pipes ≥ 90m
gas side
(mm)
liquid side
(mm)
The first line
branch pipe
gas side
(mm)
liquid side
(mm)
The first line
branch pipe
A16
Φ15.9
Φ9.5
FQZHN-01C
Φ19.1
Φ9.5
FQZHN-01C
16≤A23
Φ19.1
Φ9.5
FQZHN-01C
Φ22.2
Φ9.5
FQZHN-02C
Note: Main pipe L1 can be selected form table 2 and table 3, the larger size should be finally selected.
The straight distance between copper pipe turning and the contiguous branch pipe is at least 0.5m;
The straight distance between the contiguous branch pipes is at least 0.5m;
The straight distance which the branch pipes connected to the indoor unit is at least 0.5m;
Table4: Outdoor unit pipe connection
Piping side
MODEL
Outdoor unit pipe connection (mm)
Gas Side
Liquid Side
12kW
Φ15.9
Φ9.5
14kW
Φ15.9
Φ9.5
16kW
Φ19.1
Φ9.5
18kW
Φ19.1
Φ9.5
Outdoor Unit
(kW)
Maximum Quantity of
Indoor unit
Total Capacity of Indoor unit
12
6
45%~130%
14
6
45%~130%
16
7
45%~130%
18
9
45%~130%
If ODU connect only one IDU, the capacity of IDU should be not more than ODU.
If ODU connect more than one IDU, the capacity of each IDU should be not more than 8kW for refrigerant uniform distribution.
When capacity of indoor unit greater than the sum of 100%, capacity of indoor unit will be attenuated.
When capacity of indoor unit greater than or equal to the sum of 120%, in order to ensure the effectiveness of machine, and then
try to open the indoor units at different time.
When the capacity of indoor unit is greater than or equal to 16.8kW, the caliber of primary gas pipe should be augmented from
Φ16 to Φ19.
4.4 Remove Dirt or Water in the Piping
Make sure there is no any dirt or water before connecting the piping to the outdoor units.
Wash the piping with high pressure nitrogen, never use refrigerant of outdoor unit.
4.5 Airtight Test
Charge pressured nitrogen after connecting indoor/outdoor unit piping to do airtight test.
Cautions:
1. Pressured nitrogen [4.3MPa (44kg/cm) for R410A] should be used in the airtight test.
2. Tighten high pressure/low pressure valves before applying pressured nitrogen.
3. Apply pressure from air vent mouth on the high pressure/low pressure valves.
4. The high pressure/low pressure valves are closed when applying pressured nitrogen.
5. The airtight test should never be use any oxygen, flammable gas or poisonous gas.
4.6 Vacuum
Using vacuum pump to do the vacuum and never using refrigerant to expel the air.
Vacuum should be done from both liquid side and gas side simultaneously.

Table of Contents

Related product manuals