EasyManuals Logo

Midea MDV-V140W/DRN1 User Manual

Midea MDV-V140W/DRN1
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #80 background imageLoading...
Page #80 background image
MCAC-VTSM-2016-10 R410A All DC Inverter Mini VRF
Troubleshooting 77
4.3 E2: Communication malfunctions between indoor unit chip and outdoor unit chip.
*Outdoor unit chip refers to 0537 chip.
LED displays E2
Communication malfunctions between indoor unit chip and outdoor unit chip.
Judge 3: check the communication wire
sequence is correct or not.
Connect the wire again.
NO
Judge 4: Check whether there is disconnection.
YES
Replace
NO
Judge 2: check whether the three-cored
shielded wire is used as the communication
wire and earthed properly.
YES
Replace shielded wire or earth the wire
properly.
NO
PCB of indoor unit and outdoor unit malfunction.
Please replace.
Judge 1: Check whether the indoor unit is
power on
Plug the indoor unit in.
NO
YES

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MDV-V140W/DRN1 and is the answer not in the manual?

Midea MDV-V140W/DRN1 Specifications

General IconGeneral
BrandMidea
ModelMDV-V140W/DRN1
CategoryInverter
LanguageEnglish

Related product manuals