Installation detail 
14
 
vacuum  the  indoor  unit  through  the  maintenance  port  on  the  cut-off  valves,  or  open  the 
high-pressure  valve,  and  exhaust  the  air  through  the  maintenance  port  on  the  low-pressure 
valve(closed).  It  will  take  about  ten  seconds.  Then  screw  tightly  the  maintenance  port.    (When 
supplement  the  refrigerant,  fill  through  the  maintenance  port  of  the  low-pressure  valves  on  the 
outdoor unit ). 
e. 
Open all the valves completely before power on the system, or it will be sick for low efficiency. 
f. 
Gas leak check. Make sure no gas from connections with leak detector or soap water.   
 
6.3.2.2 Using bronze pipe selling in market 
Completely shut the cut-off valves of the outdoor unit (as ex-work status).    After the refrigerant 
pipe  has  been  connected  with  both  the  indoor  and  outdoor  unit,  let  the  air  exhaust  out  from  the 
maintenance gap    on he    low-pressure cut-off    valves of the outdoor unit.    Screw the nuts tightly 
on the maintenance gap after the air has been drained. 
6.3.2.3 To make the refrigerant pipe unblocked completely 
you should keep the cut-off valves of the outdoor unit completely open after you have finished 
the above steps (step1) or step 2)) 
Note:  Before  screwing  the  reamer  nut,  smear  the  pipe  and  the  connecting  surface  with 
refrigerant  oil;  Check  and  make  sure  there  is  no  leakage  by soap-water  or  leakage-checker  after 
connecting; 
Be sure the connecting joint on the indoor side is insulated. 
Use two wrenches to connecting the pipes. 
Tubing size  Torque 
9.52  3270~3990N.cm(333~407kgf.cm) 
12.7  4950~6030N.cm(504~616kgf.cm) 
16  6180~7540N.cm(630~770kgf.cm) 
19  9720~11860N.cm(990~12106kgf.cm) 
6.3.3  Air Purging 
When Using the Vacuum Pump 
(For method of using a    manifold valve, refer to its operation manual.) 
a. 
Completely  tighten  the  flare  nuts,  A,  B,  C,  D,  connect  the  manifold  valve  charge  hose  to  a 
charge port of the low-pressure valve on the gas pipe side. 
b. Connect the charge hose connection to the vacuum pump. 
c. Fully open the handle Lo of the manifold valve. 
d. Operate the vacuum pump to evacuate. After starting evacuation, slightly loose the flare nut of 
the Lo valve on  the  gas  pipe side  and check that  the air is  entering.(Operation noise  of    the 
vacuum    pump changes    and    a    compound meter indicates 0 instead of minus) 
e. After the evacuation is complete, fully close the handle Lo of the manifold valve and stop the 
operation  of  the  vacuum  pump.  Make  evacuation  for  15  minutes  or  more  and check  that the 
compound meter indicates    -76cmHg (-10x106Pa).