Installation detail 
13
 
Make a concrete basement to the unit by the above references. 
 
6.3  Refrigerant pipe connecting 
6.3.1  Pipe length and the elevation 
The correct refrigerant quantity filled in the 5-meter-long    pipe of the    outdoor unit is marked on 
the  Product  Data  Plate.  If  you  have  to  use  longer  pipe  for  every  meter  plus  pipe,  the  refrigerant 
should be added according to the following calculation. 
 
Standard
Pipe sizeC apacity
 
6.3.2    Piping connection 
6.3.2.1 Connecting Of Refrigerant Pipe 
a. 
Only the correctly installing of indoor and outdoor unit done, can the refrigerant pipe be connected. 
b. 
The cut-off valves are completely close before ex-work. Before connecting the refrigerant pipe, be 
careful to check whether the valves are completely close. 
c. 
The connecting procedure of refrigerant pipe: first, unscrew the two valves on the outdoor unit and 
the pipe-jointing nut on the indoor unit(please keep them care fully). Please connect the refrigerant 
pipe according to the manual, the pipe-jointing nut should be screw tightly and no leakage. Note: 
you need two wrenches to make balance. 
d. 
When  the  connecting  of  refrigerant  pipe  is  finished,  before  power  on  the  system,  you  should