Electronic function 
19
 
7.3.6  Auto Mode 
7.3.6.1 Under auto mode, the indoor fan is set to be auto. 
7.3.6.2 When entering auto mode, the heating, fan only or cooling operation will be 
automatically  chosen  according  to  the  room  temperature  T1  and  the  set 
temperature Ts. 
Condition  Mode 
T1-Ts>1°C  Cooling 
-1°C< T1-Ts<1°C  Fan 
T1-Ts<-1°C  Heating(fan for cooling only type) 
7.3.6.3 After one mode is chosen, if the condition lasts for 15 minutes, meanwhile the 
compressor doesn't start up within consecutive 15 minutes, the operation mode 
will be re-chosen according to the T1and Ts. 
7.3.6.4 If certain condition is met, then the corresponding protective function will be 
executed. 
7.3.7  Fan Only Mode 
7.3.7.1 Under this mode, four-way valve, compressor and outdoor fan are shut down. 
 
7.3.7.2 High/Low/Auto fan can be switched over through manual control. Auto fan will 
be controlled in line with cooling auto fan with temperature set to be 24C. 
7.4  Other Functions 
7.4.1  LCD display 
Mode, Set temp.,fan speed, time, timer, protection etc. 
7.4.2  Timer   
The  machine  should  be  provided  with  max.  Interval  of  24h  and  min.  resolution  ratio  of  15 
minutes.