M thermal Mono       
44    202005 
Midea M thermal Mono Engineering Data Book 
  Hold the pipe end downwards when removing burrs 
  Cover the pipe end when inserting it through a wall to prevent dust and dirt entering. 
  Use  a  good  thread  sealant  for  sealing  the  connections.  The  sealing  must  be  able  to  withstand  the  pressures  and 
temperatures of the system. 
  When  using  non-copper  metallic piping, be  sure to  insulate  the  two  kind  of  materials  from  each other  to  prevent 
galvanic corrosion. 
  For copper  is  a  soft material, use appropriate  tools for connecting the water circuit. Inappropriate tools will  cause 
damage to the pipes   
 
3.4  Water Circuit Anti-freeze Protection   
Ice formation can cause damage to the hydronic system. As the outdoor unit may be exposed to sub-zero temperatures, 
care  must  be  taken  to  prevent  freezing  of  the  system.  All  internal  hydronic  parts  are  insulated  to  reduce  heat  loss. 
Insulation must also be added to the field piping.   
  The software contains special functions using the heat pump to protect the entire system against freezing.   
When the temperature of the water flow in the system drops to a certain value, the unit will heat the water, either 
using the heat pump, the electric heating tap, or the backup heater. The freeze protection function will turn off only 
when the temperature increases to a certain value. 
  In event of a power failure, the above features would not protect the unit from freezing. 
Since a power failure could happen when the unit is unattended, the supplier recommends  use anti-freeze fluid to 
the water system or install freeze protection valves which can drain the water from the system before it can freeze. 
  Anti-freeze fluid 
Depending on the expected lowest outdoor temperature, make sure the water system is filled with a concentration 
of  glycol  as  mentioned in  the table  below.  If  the system  contains a  domestic hot water tank, then only  propylene 
glycol is suitable. If the system does NOT contain a domestic hot water tank, then either propylene glycol or ethylene 
glycol is OK. When glycol is added to the system, the performance of the unit will be affected. The correction factor 
of the unit capacity, flow rate and pressure drop of the system is listed in the table 3-3.2 and 3-3.3. 
 
Table 3-3.2: Ethylene Glycol   
Concentration 
of  ethylene 
glycol (%) 
Minimum outdoor 
temperature(° C ) 
Cooling capacity 
modification 
 
Table 3-3.3: Propylene Glycol (including the necessary inhibitors, classified as Category III according to EN1717) 
Concentration 
of  propylene 
glycol (%) 
Minimum outdoor 
temperature (° C ) 
Cooling capacity 
modification 
 
Uninhibited glycol will turn acidic under the influence of oxygen. This process is accelerated by presence of copper 
and at higher temperatures. The acidic uninhibited glycol attacks metal surfaces and forms galvanic corrosion cells 
that cause severe damage to the system. It is of extreme importance: