M thermal Mono
60 202005
Midea M thermal Mono Engineering Data Book
If set DOUBLE ZONE to YES and set ROOM TEMP. to NON, meanwhile set WATER FLOW TEMP. to YES or NON, the following
pages will be displayed. In this case, the setting value of zone 1 is T1S, the setting value of zone 2 is T1S2.
Homepage (zone 1)
Addition page (zone 2)
If set DOUBLE ZONE and ROOM TEMP. to YES, meanwhile set WATER FLOW TEMP. to YES or NON, the following page will
be displayed. In this case, the setting value of zone 1 is T1S, the setting value of zone 2 is T1S2. (The corresponding TIS2 is
calculated according to the climate related curves.)
Homepage (zone 1)
Addition page (zone 2)
(Double zone is effective)
7.9 ROOM THERMOSTAT Menu
MENU > FOR SERVICEMAN > ROOM THERMOSTAT
As an alternative to controlling space heating/cooling modes according the M
thermal units leaving water temperature and/or the room temperature detected
by the temperature sensor in the M thermal user interface, separate room
thermostat can be installed and used to control space heating/cooling modes.
In ROOM THERMOSTAT the following parameters should be set.
ROOM THERMOSTAT sets whether or not room thermostats are installed. For installations with room thermostats, select
YES. For installations without room thermostats, select NON.
ROOM THERMOSTAT = NON: No room thermostat.
ROOM THERMOSTAT = MODE SET: Room thermostat can control heating and cooling individually.
ROOM THERMOSTAT=ONE ZONE: Room thermostat provides the switch signal to unit.
ROOM THERMOSTAT=DOUBLE ZONE: Indoor unit is connected with two room thermostat.
Figure 3-7.23: ROOM THERMOSTAT menu
NON
6 ROOM THERMOSTAT
6.1 ROOM THERMOSTAT
ADJUST
Midea CAC Confidential