4.9 HF Troubleshooting
Digital display output
Description
Refrigerant system EEPROM error.
M thermal Mono stops running.
Error code is displayed on refrigerant system main control board for refrigerant system and user interface.
Possible causes
Refrigerant system main PCB EEPROM is not connected properly.
Refrigerant system main PCB damaged.
Procedure
Refrigerant system EEPROM
1
is not
connected properly
Ensure the EEPROM is connected
properly
Replace refrigerant system main PCB
Notes:
1. Refrigerant system main PCB EEPROM is designated IC23 on the refrigerant system main PCBs (labeled 29 in Figure 4-2.2 in Part 4, 2.3 “Main PCBs for
Refrigerant System, Inverter Modules and Filter Boards”), designed IC13 on the refrigerant system main PCBs (labeled 19 in Figure 4-2.4 in Part 4, 2.2
“Main PCBs for Refrigerant System, Inverter Modules and Filter Boards”), designed IC23 on the refrigerant system main PCBs (labeled 26 in Figure 4-2.6 in
Part 4, 2.2 “Main PCBs for Refrigerant System, Inverter Modules and Filter Boards”).