Midea M thermal Mono Service Manual
4.20 Inverter module Troubleshooting for single-phase models
Digital display output
Description
Inverter module protection.
M thermal Split stops running.
Specific error code L0, L1, L2, L4, L5, L8, L9 is displayed on the user interface and the main control board of refrigerant
system.
Possible causes
Inverter module protection.
DC bus low or high voltage protection.
MCE error(DC bus low or high voltage protection or software over current protection)
Zero speed protection.
Excessive compressor frequency variation.
Actual compressor frequency differs from target frequency.
High pressure protection.
PED board self checking fail.
Specific error codes for inverter module protection
Table 4-4.1: Specific error codes
Inverter module protection
DC bus low voltage protection
DC bus high voltage protection
MCE error(DC bus low or high voltage protection or software over current protection)
Compressor frequency variation greater than 15Hz within 1 second protection
Actual compressor frequency differs from target frequency by more than 15Hz protection