EasyManuals Logo

Midea MHC-V6W/D2N8-B User Manual

Midea MHC-V6W/D2N8-B
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #93 background imageLoading...
Page #93 background image
M thermal Mono
202004 91
4.21 Inverter module Troubleshooting for three-phase models
Digital display output
Description
Inverter module protection or high pressure protection.
M thermal Mono stops running.
Specific error code L0, L1, L2, L4, L5, L8 , L9 is displayed on the user interface and the refrigerant system main PCB.
Possible causes
Inverter module protection.
DC bus low or high voltage protection.
MCE error(DC bus low or high voltage protection or software over current protection)
Zero speed protection.
Excessive compressor frequency variation.
Actual compressor frequency differs from target frequency.
High pressure protection.
Contactor stuck or 908 self checking fail.
Specific error codes for inverter module protection
Table 4-4.4: Specific error codes
Specific error code
Content
L0
Inverter module protection
L1
DC bus low voltage protection
L2
DC bus high voltage protection
L4
MCE error(DC bus low or high voltage protection or software over current protection)
L5
Zero speed protection
L8
Compressor frequency variation greater than 15Hz within one second protection
L9
Actual compressor frequency differs from target frequency by more than 15Hz protection
Midea CAC Confidential

Other manuals for Midea MHC-V6W/D2N8-B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MHC-V6W/D2N8-B and is the answer not in the manual?

Midea MHC-V6W/D2N8-B Specifications

General IconGeneral
BrandMidea
ModelMHC-V6W/D2N8-B
CategoryAir Conditioner
LanguageEnglish

Related product manuals