4.21 Inverter module Troubleshooting for three-phase models
Digital display output
Description
Inverter module protection or high pressure protection.
M thermal Mono stops running.
Specific error code L0, L1, L2, L4, L5, L8 , L9 is displayed on the user interface and the refrigerant system main PCB.
Possible causes
Inverter module protection.
DC bus low or high voltage protection.
MCE error(DC bus low or high voltage protection or software over current protection)
Zero speed protection.
Excessive compressor frequency variation.
Actual compressor frequency differs from target frequency.
High pressure protection.
Contactor stuck or 908 self checking fail.
Specific error codes for inverter module protection
Table 4-4.4: Specific error codes
Inverter module protection
DC bus low voltage protection
DC bus high voltage protection
MCE error(DC bus low or high voltage protection or software over current protection)
Compressor frequency variation greater than 15Hz within one second protection
Actual compressor frequency differs from target frequency by more than 15Hz protection