74 Troubleshooting
4.13 P5: Condenser high temperature protection
When condenser temperature is higher than 62 degrees for 3 seconds, the unit will stop operating.
When pipe temperature outside is lower than 52 degrees, the unit will resume operate.
Condenser T3 high temperature protection
Check whether condenser temperature is higher than
62 degrees for 3 seconds.
Check whether the resistance of condenser
temperature sensor is correct.
Replace the temperature sensor
Judge 1: whether outdoor temperature is too high(higher than
Judge 2: whether heat exchanger needs cleaning.
Judge 3: if refrigerant pipe is blocked or not?
Remove the refrigerant pipe and then
use high pressure nitrogen or
refrigerant to blow the pipe.
Vacuumed the pipe then add the
refrigerant again.