Loading...
46°C
-15°C
COOLINGMODE
27°C
-15°C
HEATING MODE
The longest piping length is 70m
The first branch joint to the
farthest IDUis 20m
The IDUto the nearest
branch joint is 15m
Leveldifference between IDUand ODUis 30m
Leveldifference between IDUs is 8m
Piping Length
Permitted Value
Total piping length (Actual)
100m
Longest piping
length
Actual
60m
Equivalent
70m
The first branch joint to the farthest IDU
20m
The IDU to the nearest branch pipe
15m
Level difference
between ODU~IDU
ODU up
30m
ODU down
20m
Level difference between IDU~IDU
8m