MCAC-UTSM-2008-05  Troubleshooting 
Outdoor Units  65 
8. P3 malfunction 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
LED indicates P3
Outdoor unit current protection 
Judge 1: Check whether the input current of the power supply wire 
is more than 18A   
Check whether the refrigerant system is ok 
Yes 
Judge 2: Check whether the outdoor ambient temperature is too high   
 
Yes 
Stop the unit 
Replace outdoor main board 
No 
No 
Judge 3: Check whether the outdoor unit is bad ventilation 
Yes 
Make the outdoor unit ventilate well
No 
Judge 4: Check whether the heat exchanger is dirty 
Yes 
Clean the heat exchanger 
No 
Judge 5: The refrigerant pipe is blocked 
Yes 
Drop refrigerant, then use the high pressure 
nitrogen or refrigerant to blow pipe, 
vacuumize and add the refrigerant again