Troubleshooting  MCAC-UTSM-2008-05 
66  Outdoor Units 
9. P4 malfunction 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
LED indicates P4
Compressor discharge temperature protection 
Check whether the compressor discharge temp. more than 115°C ? 
No 
Check whether the wiring connection is right 
between compressor discharge temp. 
sensor and PCB according to wiring 
diagrams 
 
Yes 
Validate: Check whether the resistance of compressor 
discharge temp. sensor is right refer to the Annex 2 
No 
Correct the wiring connection 
Yes 
Replace outdoor main board 
Judge: The discharge temp. sensor is broken 
No 
Replace the compressor 
discharge temp. sensor 
Check whether the refrigerant is leakage 
Stop leaking and add refrigerant 
Yes 
Yes