Page 20 
Refrigerant Piping 
Connection
Table 7.2 
Permitted length
Piping 
length 
Total piping length 18K+18K 30/98’ L+Max 
(L1, L2)
24K+24K
30K+30K
50/164’
(farthest distance from 
the line pipe branch)  
15/49’ L1, L2
(farthest distance from 
the line pipe branch) 
10/32.8’ L1-L2
Drop 
height 
Drop height between 
indoor and outdoor unit  
20/65.6’ H1
Drop height between 
two indoor units  
0.5/1.6’ H2
Refrigerant Piping Connection Instructions
 CAUTION
•  The branching pipe must be installed 
horizontally. An angle of more than 10° may 
cause malfunction. 
•  DO NOT install the connecting pipe until 
both indoor and outdoor units have been 
installed.
 
•  Insulate both the gas and liquid piping to 
prevent water leakage. 
Step1: Cut pipes
When preparing refrigerant pipes, take extra 
care to cut and flare them properly. This will 
ensure efficient operation and minimize the 
need for future maintenance.   
1.
  Measure the distance between the indoor 
and outdoor units. 
2.
  Using a pipe cutter, cut the pipe a little 
longer than the measured distance. 
 CAUTION
DO NOT deform pipe while cutting. Be extra 
careful not to damage, dent, or deform the pipe 
while cutting. This will drastically reduce the 
heating efficiency of the unit. 
1. Make sure that the pipe is cut at a perfect 90° 
angle. Refer to Fig. 7.5 for examples of bad cuts 
Oblique
Rough
Warped
90°
Fig. 7.5
Step 2: Remove burrs.
Burrs can aect the air-tight seal of refrigerant 
piping connection. They must be completely 
removed. 
1. Hold the pipe at a downward angle to 
prevent burrs from falling into the pipe. 
2. Using a reamer or deburring tool, remove 
all burrs from the cut section of the pipe. 
Pipe
Reamer
Fig. 7.6
Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight 
seal.
1. After removing burrs from cut pipe, seal 
the ends with PVC tape to prevent foreign 
materials from entering the pipe. 
2. Sheath the pipe with insulating material.
3. Place flare nuts on both ends of pipe. 
Make sure they are facing in the right 
direction, because you can’t put them on 
or change their direction after flaring. See 
Fig. 7.7  
Flare nut
Copper pipe
Fig. 7.7