Page 27 
Air Evacuation
Air Evacuation
Safety Precautions
 CAUTION
•  Use a vacuum pump with a gauge reading 
lower than -0.1MPa and an air discharge capacity 
above 40L/min. 
•  The outdoor unit does not need vacuuming.
DO NOT open the outdoor unit’s gas and 
liquid stop valves.
 
•  Ensure that the Compound Meter reads 
-0.1MPa or below after 2 hours. If after 
three hours of operation and the gauge 
reading is still above -0.1MPa, check if there 
is a gas leak or water inside the pipe. If 
there is no leakage, perform another 
evacuation for 1 or 2 hours.    
•  DO NOT use refrigerant gas to evacuate the 
system. 
 
Evacuation Instructions
Before using manifold gauge and vacuum pump, 
read their operation manuals to familiarize 
yourself with how to use them properly.  
Manifold Gauge
Compound gauge
-76cmHg
Low pressure valve
High pressure valve
Charge hose
Charge hose
Vacuum pump
Pressure gauge
Low pressure valve
Fig. 9.1
1. Connect the charge hose of the manifold 
gauge to service port on the outdoor unit’s 
low pressure valve. 
2. Connect another charge hose from the 
manifold gauge to the vacuum pump. 
3. Open the Low Pressure side of the manifold 
gauge.Keep the High Pressure side closed. 
4. Turn on the vacuum pump to evacuate the 
system.
5. Run the vacuum for at least 15 minutes, or 
until the Compound Meter reads -76cmHG 
(-1x105Pa). 
6. Close the Low Pressure side of the manifold 
gauge, and turn o the vacuum pump. 
7. Wait for 5 minutes, then check that there has 
been no change in system pressure. 
NOTE: If there is no change in system pressure, 
unscrew the cap from the packed valve (high 
pressure valve). If there is a change in system 
pressure, there may be a gas leak.   
8. Insert hexagonal wrench into the packed valve 
(high pressure valve) and open the valve by 
turning the wrench in a 1/4 counterclockwise 
turn. Listen for gas to exit the system, then 
close the valve after 5 seconds.   
Flare nut
Cap
Valve stem
Fig. 9.2
9. Watch the Pressure Gauge for one minute to 
make sure that there is no change in pressure. 
The Pressure Gauge should read slightly higher 
than atmospheric pressure.  
10. Remove the charge hose from the service port.
11. Using hexagonal wrench, fully open both the 
high pressure and low pressure valves. 
OPEN VALVE STEMS GENTLY
When opening valve stems, turn the hexagonal 
wrench until it hits against the stopper. DO NOT 
try to force the valve to open further.   
 
12. Tighten valve caps by hand, then tighten it 
using the proper tool. 
9