DM13-01.01.16en Air-cooled Package
Service manual 71
3.5.1 Size of Outdoor Unit Pipes and Piping Methods
1) Size of outdoor unit pipes and piping methods
Model Gas side Liquid side
MOV-76CN1-C Φ22
Φ9.52
MOV-76HN1-C Φ22
Φ9.52
MOV-96CN1-C Φ25
Φ9.52
MOV-96HN1-C Φ25
Φ9.52
MOV-120CN1-C Φ28.6
Φ12.7
MOV-120HN1-C Φ28.6
Φ12.7
2) Allowed length of refrigerant pipe and height difference (Fig-22)
Outdoor unit
Max. pipe length L 50m
H
e
i
g
h
t
d
i
f
f
e
r
e
n
c
e
b
e
t
w
e
e
n
i
n
d
o
o
r
u
n
it
a
n
d
o
u
td
o
o
r
u
n
i
t
H
3
0
m
In
d
o
o
r
u
ni
t
Fig-22
Table 1:
76000 96000 50000
Btu/h
120000
Btu/h
Max. equivalent length of pipe (L) 50m 50m
Max. height difference
Height difference between
indoor unit and outdoor unit (H)
Outdoor upper 30m 30m
Outdoor lower 30m 30m

Other manuals for Midea MOV-120CN1-C

Related product manuals