126
8.8.2. Forced Auto
8.8.2.1 Remote control signal can be received in forced auto mode. When receiving the signals, the
forced auto mode will be canceled and the A/C changes to remote control status and performs
operation as the signals indicates.
8.8.2.2 The system performs control according to the remote control auto mode with a set temperature of
24°c.
8.9 Timer
24 hours timer on or off.
8.10 Protecting Function
8.10.1 Compress with a delay of 3 minutes.
8.10.2 Sensor open and break protection
8.10.3 EEPROM error protection.
8.10.4 Current protection function.
I=Current value Outdoor fan Compressor
I< I3 On On
I3<I< I2 Off On
I2<I< I1 Off Turn off compressor after 5 minutes
Current up
I>I1 Off Turn off compressor after 3 seconds
I>I1 Off Turn off compressor after 3 seconds
I2<I< I1 Off Turn off compressor after 5 minutes
I4<I< I2 Off On
Current up down
I< I4 On On
8.10.5 Out door unit protection
Refer to clause 7.2 Outdoor unit
8.11 Auto restart Function
8.12 Models and Parameters
Model MSG-36CR MSG-36HR
I3SEC 34A 34A
I5MIN 32A 32A
IFAN 25A 25A
IRESTORE 22A 22A
TE1 30
TE2 37
TE3 34
TE4 24
TE5 2 2
TE6 12 12
TE7 63
TE8 54
TE9 50
TE10 70
TE11 65
TE14 32
TE16 34