7.Troubleshooting(Capacity less than 18000Btu/h)
7.1 For all cooling only model
Failure phenomenon Operation lamp Timer lamp
Indoor fan speed has been out of control for over 1 minute X
Indoor room temp. or evaporator sensor is open circuit or short circuit On
Over current protection of the compressor occurs 4 times X
EEPROM error On
No over-zero signal
r Extinguish
Flash at 5Hz
7.2 For all heat pump model
Failure phenomenon Operation lamp Timer lamp Defrosting lamp
Over current protection of the compressor occurs 4 times X
Indoor fan speed has been out of control for over 1 minute X
No over-zero signal
Temp. sensor on indoor evaporator is open circuit or short circuit X X
Indoor room temp. sensor is open circuit or short circuit X X
EEPROM error On X
r Extinguish
Flash at 5Hz
8. Electric control functions
8.1 Electric Control working environment
8.1.1 Input voltage: 175~253V
8.1.2 Input power frequency:50Hz
8.1.3 Ambient temperature: -7°C~+43°C
8.1.4 Indoor fan normal working amp is less than 1A,
8.1.5 Outdoor fan. Normal working amp is less than 1.5A
8.1.6 Four-way valve normal working amp is less than 1A.
8.1.7 Swing motor: DC12V.
8.1.8 Compressor: single-phase power supply. Its normal working amp is less than 15A
8.2 Proper symbols and their meanings:
TA: Indoor ambient temperature
TE: Indoor evaporator temperature
TS: Setting temperature through the remote controller
I
3sec
: Self-protection amp of compressor, continue three seconds until turns off the
compressor.
I
5MIN
: Self-protection amp of compressor, continue five minutes until turns off the compressor.
I
FAN
: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to
lower wind.
I
RESTORE
: Amp self-protection return value