189
7.Troubleshooting
7.1 Indoor Unit Error Display Function
LED4 operation LED2 defrosting LED1 timer LED4 auto
LED2
defrost
LED1
Timer
LED3
Auto
LED4
operation
LED STATUS
X X O Mold protection
O X X Compressor top protection against temperature
X O X Open or short circuit of outdoor temperature sensor
X O O Over load or too low voltage protection
O O O
Room temperature or evaporator temperature sensor open
or short circuit of
O O Fan speed beyond control
X O Zero-crossing examination error
O X Temperature fuse protection
X X EEPROM data error
O X Types doesn't match
Indoor / outdoor units communication protection
O (on) X (off) (flash)