23
8.7 Dehumidifying mode
8.7.1 The 4-way valve is off at dehumidifying mode
8.7.2 Compressor and Indoor Fan actions in dehumidifying mode
Repeat on and off cycle.
8.7.3 Low room temperature protection:, When room temperature decreases to below 10,
compressor and outdoor fan will stop(indoor fan is Breeze). Dehumidifying operation will
be resumed when room temperature restores to over 13.
8.7.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the
same as that of cooling mode.
8.8 Heating mode
8.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting
mode. 4-way valve must delay 2 minutes compared with compressor if the
compressor changed into non-heating mode or turned off. 4-way valve doesn't
delay in dehumidifying mode.
8.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in
heating mode, except for the defrosting mode or the end of defrost.
8.8.3 Action of compressor at heating mode: compressor must run for 7 minutes after
starting and then judge temperature. Meanwhile other protections are still valid.
Condition Compressor Outdoor fan
T> Ts+3 Off Off Room temp. up
T<Ts+3 On On
T< Ts+2 On On Room temp. down
T>Ts+2 Off Off
8.8.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but
Anti-cold wind function prevails.
NO Conditions
Indoor Fan Compressor and Outdoor Fan
1 TA TS+2
LOW
BREEZE
ON 6 minutes
OFF 4minutes
2
TS TATS+2
LOW
BREEZE
ON 5minutes
OFF 5minutes
3
TA TS
LOW
BREEZE
ON 4minutes
OFF 6minutes