193
8.4.6 At dehumidifying mode, the power voltage and outdoor temperature limitation to the highest
frequency when compressor starts and operates is the same as that at cooling mode.
8.5 Heating Mode Function Requirement
8.5.1 At heating mode, the 4 way valve is on, during defrosting operation, it is off.
8.5.2 Outdoor fan usually turns on or off in accordance with the action of compressor, except for
defrosting and ending of the defrost.
8.5.3 Indoor fan action:
Anti-cold air control
8.5.4 Indoor fan can be set by remote control to any mode like High/Mid/Low/Auto, however anti-cold
air function comes first.
Auto fan
Temperature of heat exchanger
37°c
Set rotational speed
34°c
33°c
breeze
18°c
fan off
Room temperature - set temperature
-0.5
Low
-1.0
-1.5 Mid
-2.0
High