Midea V6-i Series Service Manual
2.11 F6: Electronic expansion valve connection error
Digital display output 2.11.1
Description 2.11.2
Electronic expansion valve connection error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.11.3
Trigger condition: The main control board cannot receive the feedback signal of EXV.
Recover condition: The main control board can receive the feedback signal of EXV.
Reset method: When the main control board can receive the feedback signal of EXV, F6 flashes, a manual system
restart id required before the system can resume operation.
Possible causes 2.11.4
Electronic expansion valve coil not connected properly or has malfunctioned.
Damaged main PCB.