Table 3-4.3: Phenomena need to contact Midea service agency
Detect and settle measure
Compressor is unable to drive
Connected with wrong phase sequence.
2. Wire connection is loosening.
1. Fixing screw of the fan is loosening.
Re-fasten the fixing screw of the fan.
2. Fan blade touched the cover shell or screen
3. The fan operated unsteadily.
Abnormal noise given out from
compressor
1. Liquid refrigerant flows into compressor and
produces liquid strikes.
Check the EXV, and whether the
temperature sensor loosen and repair.
2. Damages of the compressor inner
components.
Water pump not operated or
abnormal operated
3. There is gas in the water pipe.
Compressor ON and OFF
frequently
1. Bad circulation of water system.
Blocked the water system or has air in
the water system. Check the water
pump, valves, pipeline, and clean the
water filter or drain off the air.
Adjust the load or add stored energy
device.
Compressor operated with no
heating
Check, repair and replenish the
refrigerant.
No obvious heating effect of the
unit
1. Bad thermal insulation of water system.
Enlarge the thermal insulation of the
system.
2. Bad heat exchanging of evaporator.
Check the air inlet and outlet whether
are normal and clean the evaporator.
Check whether has refrigerant leakage.
4. The water side heat exchanger has blocked.
Clean or change the heat exchanger.