MCAC-UTSM-2014-03 R410A 380~415V 3Ph 50Hz TempMaker Series Split AC
106
10.6 Outdoor unit malfunction and protection codes
Type
LED1
LED2
Phase sequence or lack of phase.
☆★
Communication error.
☆☆★
Condenser temperature sensor error.
☆☆☆★
Ambient temperature sensor error
☆☆☆☆★
System low pressure protection.
O
☆★
Three times low pressure protections within 1 hour.
☆★
System hi-pressure protection, hi-temperature protection
of compressor discharger.
O
☆☆★
Current overload protection.
O
☆☆☆★
High temperature protection of condenser.
O
☆☆☆☆★
Note:
: Light
: Extinguishing
: Rapidly flash
:Slowly flash
When the outdoor unit protections of temperature or system pressure are triggered
three times within 1 hour, the unit will resume after power on again.
Phase sequence or lack of phase