V8 Mini R410A VRF 50Hz
29
Part 2
-
Outdoor Unit Engineering Data
7 Functional Components and Safety Devices
Table 2-7.1: 80/100/120/140/160 model functional components and safety devices
Item
80
100
120
140
160
Compressor
Discharge pipe temperature sensors
90°C = 5kΩ ± 3%
Crankcase heater
25W
Fan motor
Safety thermostat
On
100°C
Off
80°C
System
High pressure switch
Off: 4.3 (±0.1) MPa
/ On: 3.2 (±0.1) MPa
Heat exchanger temperature sensor
25°C = 10
Outdoor ambient temperature sensor
25°C = 10