EasyManuals Logo

Midea VC Pro Series User Manual

Midea VC Pro Series
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #157 background imageLoading...
Page #157 background image
VC Pro VRF 50/60Hz
157
Part 3 - System Design and Installation
4.5 Refrigerant Piping Selection Example
The example below illustrates the piping selection procedure for a system consisting of three outdoor units (32HP + 22HP +
12HP) and 17 indoor units. The system's equivalent length of all liquid pipes is in excess of 90m; the piping between the
farthest indoor unit and the first indoor branch joint is less than 40m in length; and each indoor auxiliary pipe (from each
indoor unit to its nearest branch joint) is less than 10m in length.
Figure 3-4.4: Refrigerant piping selection example
Step 1: Select indoor auxiliary pipes
Indoor units N
1
to N
6
, N
8
to N
11
and N
13
to N
17
are of capacity 5.6kW or greater and their indoor auxiliary pipes are less
than 10m in length. Refer to Table 3-4.8. Indoor auxiliary pipes a to f, h to k, and m to q are Φ15.9 / Φ9.53.
Indoor units N
7
and N
12
are of capacity less than 4.5kW and their indoor auxiliary pipes are less than 10m in length.
Refer to Table 3-4.8. Indoor auxiliary pipes g and l are Φ12.7 / Φ6.35.
Step 2: Select indoor main pipes and indoor branch joints B to P
The indoor units (N
3
and N
4
) downstream of indoor branch joint E have total capacity of 14 + 7.1 = 21.1kW. Refer to
Table 3-4.4. Indoor main pipe L
5
is Φ19.1 / Φ9.53. Indoor branch joint E is FQZHN-01D.
The indoor units (N
1
to N
8
) downstream of indoor branch joint B have total capacity of 14 x 5 + 11.2 + 7.1 + 2.8 = 91.1kW.
Refer to Table 3-4.4. Indoor main pipe L
2
is Φ31.8 / Φ19.1. Indoor branch joint B is FQZHN-03D.
The other indoor main pipes and indoor branch joints are selected in the same fashion.
Step 3: Select main pipe and indoor branch joint A
The indoor units (N
1
to N
17
) downstream of indoor branch joint A have total capacity of 14 x 9 + 11.2 x 2 + 7.1 x 2 + 5.6
x 2 + 2.8 x 2 = 179.4kW. The system's equivalent length of all liquid pipes is in excess of 90m. The total capacity of the
outdoor units is 32 + 22 + 12 = 66HP. Refer to Tables 3-4.4 and 3-4.5. Main pipe L
1
is the larger of Φ41.3 / Φ19.1 and
Φ44.5 / Φ19.1, hence Φ44.5 / Φ19.1. Indoor branch joint A is FQZHN-05D.
Step 4: Select outdoor connection pipes and outdoor branch joints
The master unit is 32HP and the slave units are 22HP and 12HP. Refer to Table 3-4.6. Outdoor connection pipes g1 is
Φ25.4 / Φ12.7, g2 is Φ31.8 / Φ15.9 and g3 is Φ38.1 / Φ19.1.
Refer to Table 3-4.6. Outdoor connection pipe G
1
is Φ41.3 / Φ22.2.
There are three outdoor units in the system. Refer to Table 3-4.7. Outdoor branch joints S and R are FQZHW-03N1E.
N1
(140)
N4(140)
N9
(112)
N10
(140)
N12
(28)
N13
(140)
N16
(56)
N15
(140)
N3(71)
N7(28)
N6
(140)
N8(140)
N14
(56)
N17
(140)
A
B
I
J
N
K
O
C
F
H
E
L1
L2
L3
L5
L7
L8
L11
L12
L13
L15
L14
L16
L9
a
c
d
f
g
h
j
l
m
n
o
p
q
k
S
R
g1
g2
g3
G1
D
N2
(140)
b
L4
N5
(112)
G
L6
e
N11
(71)
i
L
L10
M
P
W3
(16)
W2
(22)
W1
(26)
Legend
L
1
Main pipe
L
2
to L
16
Indoor main pipes
a to q
Indoor auxiliary pipes
A to P
Indoor branch joints
L, M
Outdoor branch joints
g1 to g3, G
1
Outdoor connection
pipes
Figures in parentheses indicate indoor unit
capacity indexes.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea VC Pro Series and is the answer not in the manual?

Midea VC Pro Series Specifications

General IconGeneral
BrandMidea
ModelVC Pro Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals