VC Pro VRF 50/60Hz
31
Part 2 - Outdoor Unit Engineering Data
84-90HP
Table 2-1.12: 84-90HP specifications
HP
84
86
88
90
Model name
MVC-2355WV2GN1
MVC-2420WV2GN1
MVC-2485WV2GN1
MVC-2550WV2GN1
Combination type
28HP+28HP+28HP
30HP+28HP+28HP
30HP+30HP+28HP
30HP+30HP+30HP
Power supply
V/Ph/Hz
380-415V 3N~50/60HZ
Cooling
1
Capacity
kW
235.5
242.0
248.5
255.0
kBtu/h
804.3
826.5
848.7
870.9
Power input
kW
78.24
81.67
85.10
88.53
EER
3.01
2.96
2.92
2.88
Connected
indoor unit
Total capacity
50-130%
Maximum quantity
64
Compressor
Type
DC inverter
Quantity
6
Oil type
FV 50s
Start-up method
Soft start
Fan
Type
DC
Quantity
6
Motor output
kW
0.56×6
Static pressure
Pa
20 default;60 customization option
Airflow rate
m3/h
61800
Drive type
20 default;60 customization option
Refrigerant
Type
R410A
Factory charge
kg
19×3
Pipe
connections
2
Liquid pipe
mm
25.4
Gas pipe
mm
50.8
Sound pressure level
3
dB(A)
68
Net dimensions (W×H×D)
mm
(1585×1615×765)×3
Packed dimensions (W×H×D)
mm
(1650×1810×840)×3
Net weight
kg
338×3
Gross weight
kg
362×3
Ambient temp.
Cooling
o
C
-5 to 55
Notes:
1. Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Diameters given are those of the unit's accessories.
3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.