Installation
33
f
A power cord is required to connect the hood to the socket in the ceiling. With
e
xtraction mode flexible ducting is also required.
Exhaust connection 6" (150 mm)
Distance between cooktop and ventilation hood (S)
Provided a larger distance is not given by the manufacturer of the cooktop,
foll
ow the minimum safety distances between a cooktop and the bottom of the
hood.
Please also observe the information contained in the "IMPORTANT SAFETY
INS
TRUCTIONS" section.
Minimum distance S
Cooking appliance Miele
appliance
Non-Miele
appliance
Electric/Induction cooktop 24" (610 mm)
Electric grill, deep fat fryer (electric) 26" (660 mm)
Multi-burner gas cooktop
43,000 B
TU/hr (12.6 W),
no burner > 15,000 BTU/hr (4.5 kW).
26" (660 mm) 30" (760 mm)
Multi-burner gas cooktop
73,800 B
TU/hr (21.6 W),
no burner > 16,500 BTU/hr (4.8 kW)
30" (760 mm)
Multi-burner gas cooktop
> 73,800 B
TU/hr (21.6 W),
or one of the burners > 16,500 BTU/hr (4.8 kW)
Not possible
Single-burner gas cooktop
20,500 B
TU/hr (6 kW)
26" (660 mm) 30" (760 mm)
Single-burner gas cooktop
27,600 B
TU/hr (8.1 kW)
30" (760 mm)
Single-burner gas cooktop
> 27,600 B
TU/hr (8.1 kW)
Not possible