NOTE: The parameter version of the data file must match the parameter version of the drive
that the EPM is to be installed into. If not, the drive will display a “cF” fault and will not
operate. For example, if an EPM with a parameter version “309” data file is installed in a
version “306” dive, the drive will display a “cF” fault. Refer to the AC100 or AC200 Series
Installation and Operation Manual for more information on the “cF” fault.
Follow the procedure below to copy a data file to the target EPM:
1. Install the target EPM that will receive the data into the EPM PORT.
2. Use the MENU key to scroll to FILE TO EPM.
3. Press ENTER. The display will show the file name and parameter version number of the
last data file that was selected.
If the file that appears is the desired one, go to Step 5.
4. Press ENTER. A blinking cursor will appear on the right side of the display.
Use the V and W keys to scroll through the data file.