Abnormalpointsanddetectionmethods Causesandcheckpoints
AbnormalifovercurrentofDCbusorcompressorisdetectedafter30
secondssincethecompressorstartsoperating.
Closedoutdoorstopvalve
Decreaseofpowersupplyvoltage
Looseness,disconnection,orwrongphaseof
compressorwiringconnection
Model selection error on indoor controller board or
outdoor multi controller circuit board
Defectivecompressor
Defectiveoutdoorpowercircuitboard
Defective outdoor multi controller circuit board
Malfunction of indoor/outdoor unit fan
Short-cycle of indoor/outdoor unit
●Diagnosisofdefectives
MakesuretoturnthepowerOFFbeforeconnecting/disconnectinganyconnectors,orreplacingboards.
Diagnosis Remedy
4210
(UP)
Compressorovercurrentinterruption
Chart 1 of 2
Yes
Yes
Yes
No
No
No
Isthestopvalve
(liquid/gas)
fully
open?
Isthepowersupplyvoltagenormal?
Aretheysetproperly?
Openthestopvalve
(liquid/gas)
fully.
•
Check the looseness, disconnection, or
breakageofcompressorwiring.
•Ensurepowersupplyfromthefacility.
(Checkforpowersupplyopenphase.)
Set the model selection correctly.
Checktheoutdoorstopvalve.
Checkwhetherthepowersupplyvoltageis
normal or not.
Checkifthemodelselectionswitchisset
correctly on the indoor controller board or
outdoor multi controller circuit board.
TurnthepowerOFFtocheckfor
looseness,disconnection,orwrongphases
ofthecompressorwiring.
Continuetothenextpage