8-1-2. Countermeasures for Error During Test Run
•Ifaproblemoccursduringtestrun,acodenumberwillappearontheremotecontroller(orLEDontheoutdoorunit),andthe
airconditioningsystemwillautomaticallyceaseoperating.
Determinethenatureoftheabnormalityandapplycorrectivemeasures.
1 2 3 4 5 6 7 8
[Example]
When the compressor and
SV1 are turned during cooling
operation.
Bit
Indication
1
Compressor
operated
2
52C
3
21S4
4
SV1
5
(SV2)
6
—
7
—
8
Always lit
• Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch
(SW1) and LED1, LED2 (LED indication) found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF.
• During normal operation
The LED indicates the drive state of the controller in the outdoor unit.
Check
code
(2 digits)
Check
code
(4 digits)
Trouble
Detected Unit
Remarks
Indoor Outdoor
Remote
Controller
Ed 0403 Serial communication error
Outdoor unit outdoor multi controller circuit board
–Powercircuitboardcommunicationtrouble
U2 1102 Compressortemperaturetrouble
Check delay code 1202
UE 1302 Highpressuretrouble
Check delay code 1402
U7 1500 Superheatduetolowdischargetemperaturetrouble
Check delay code 1600
U2 1501
Refrigerant shortage trouble
Check delay code 1601
Closed valve in cooling mode
Check delay code 1501
P6 1503 Freezeprotectionofbranchboxorindoorunit
EF 1508 4-wayvalvetroubleinheatingmode Check delay code 1608
L6 2135 Circulationwaterfreezeprotection
PA 2500 Waterleakage
P5 2502 Drainoverowprotection
P4 2503 Drain sensor abnormality
UF 4100 Compressorcurrentinterruption(lockedcompressor) Check delay code 4350
Pb 4114 Fan trouble (Indoor unit)
UP 4210 Compressorovercurrentinterruption
U9 4220
Voltageshortage/overvoltage/PAMerror/L1openphase/primary
currentsensorerror/powersynchronizationsignalerror
Check delay code 4320
U5 4230 Heatsinktemperaturetrouble
Check delay code 4330
U6 4250 PowermoduletroubleorOvercurrenttrouble
Check delay code 4350
U8 4400 Fan trouble (Outdoor unit)
Check delay code 4500
U3 5101
Airinletthermistor(TH21)open/short
Compressortemperaturethermistor(TH4)open/short
Check delay code 1202
U4 5102
Liquidpipetemperaturethermistor(TH22)open/short
Suctionpipetemperaturethermistor(TH6)open/short Check delay code 1211
U4 5103 Gaspipetemperaturethermistor(TH23)open/short
U4 5105 Outdoorliquidpipetemperaturethermistor(TH3)open/short Check delay code 1205
U4 5106 Ambienttemperaturethermistor(TH7)open/short
Check delay code 1221
U4 5109 HICpipetemperaturethermistor(TH2)open/short
Check delay code 1222
U4 5110 Heatsinktemperaturethermistor(TH8)open/short
Check delay code 1214
F5 5201 Highpressuresensor(63HS)trouble
Check delay code 1402
F3 5202 Lowpressuresensor(63LS)trouble
Check delay code 1400
UH 5300 Primary current error
Check delay code 4310
P4 5701 Contactfailureofdrainoatswitch
A0 6600 Duplexaddresserror Only M-NET Remote controller is detected.
A2 6602 Transmissionprocessorhardwareerror
Only M-NET Remote controller is detected.
A3 6603 Transmission bus BUSY error
Only M-NET Remote controller is detected.
A6 6606 Signalcommunicationerrorwithtransmissionprocessor
Only M-NET Remote controller is detected.
A7 6607 No ACK error
Only M-NET Remote controller is detected.
A8 6608 Noresponseframeerror
Only M-NET Remote controller is detected.
E0/E4 6831 MA communication receive error
Only MA Remote controller is detected.
E3/E5 6832 MA communication send error
Only MA Remote controller is detected.
E3/E5 6833 MA communication send error
Only MA Remote controller is detected.
E0/E4 6834
MA communication receive error
Only MA Remote controller is detected.
EF 7100 Totalcapacityerror
EF 7101 Capacitycodeerror
EF 7102 Connectingexcessivenumberofunitsandbranchboxes
EF 7105
Address setting error
EF 7130
Incompatibleunitcombination
Notes:
1. When the outdoor unit detects No ACK error/No response error, an object indoor unit is treated as a stop, and not assumed to be abnormal.
2. The check codes displayed on the units may be different between the error source and others. In that case, please refer to the check code
of error source by displayed attribute and address.
3. Refer to the service manual of indoor unit or remote controller for the detail of error detected in indoor unit or remote controller.