Abnormal points and detection methods Causes and checkpoints
Abnormalifthedataofunit/transmissionprocessorwerenotnormally
transmitted.
Abnormaliftheaddresstransmissionfromtheunitprocessorwasnot
normally transmitted.
Accidental disturbance such as noise or lightning
surge
Hardwaremalfunctionoftransmissionprocessor
●Diagnosisofdefectives
MakesuretoturnthepowerOFFbeforeconnecting/disconnectinganyconnectors,orreplacingboards.
Diagnosis Remedy
6606
(A6)
Signalcommunicationerrorwithtransmissionprocessor
Yes
No
Doesitoperatenormally?
Replacethecontroller.
(Defect of error source controller).
There is no abnormality on the AC unit.
Itmightbecausedbyanexternalnoise,socheck
the transmission line to remove the factor(s).
TurnthepowerOFFofindoor/outdoorunit,Fresh
Master, Lossnay and remote controller simultaneously
for2minutesormore,thenturnthepowerbackON.
85