Abnormal points and detection methods Causes and checkpoints
(1)AbnormalifTH4fallsintofollowingtemperatureconditions;
●exceeds105
[221°F]continuouslyfor5minutes
●exceeds115 [239°F]
TH4:Thermistor<Compressor>
LEV:Linearexpansionvalve
Malfunctionofstopvalve
Over-heatedcompressoroperationcausedby
shortage of refrigerant
Defective thermistor
Defective outdoor multi controller circuit board
LEVperformancefailure
Defective indoor controller board
Clogged refrigerant system caused by foreign
object
Refrigerant shortage
(Refrigerantliquidaccumulationincompressorwhile
indoor unit is OFF/thermo-OFF.)
●Diagnosisofdefectives
MakesuretoturnthepowerOFFbeforeconnecting/disconnectinganyconnectors,orreplacingboards.
Diagnosis Remedy
1102
(U2)
Compressortemperaturetrouble
Yes
Yes
No
Yes
Yes
No
No
No
Is5101displayedwhenrestarted?
Istheoutdoorstopvalve(liquid/gas)
fullyopen?
Is there a refrigerant leak?
Is there any abnormality on
connectors/wiressuchasadisconnection,
half-disconnection or breakage?
Checktheconnectionforthermistorwiring
and indoor controller board connector.
Refer to the diagnosis of check code 5101.
Openthestopvalve(liquid/gas)fully.
Repairtherefrigerantleakage.
Connecttheconnectorproperly
(Repairorreplaceitincaseofabreakage).
(5101)
(1102)
(no leak)
Continuetothenextpage
Chart 1 of 2