Why Mitsubishi Electric FR-A820-00046 Inverter motor does not run at the correct speed?
- SSamantha CarterAug 3, 2025
If the Mitsubishi Electric Inverter's motor speed doesn't match the command speed, first verify that the speed command from the controller is correct and implement EMC measures to reduce noise. If the command speed and the speed recognized by the inverter are different, adjust the bias and gain (Pr. 125, Pr. 126, C2 to C7, C12 to C15) of the speed command again. Also, check the setting of Pr. 369 (Pr. 851) "Number of encoder pulses" (vector control).