EasyManua.ls Logo

Mitsubishi Electric FX3S Series - Page 217

Mitsubishi Electric FX3S Series
282 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B - 173
A
Common Items
B
Built-in
Positioning
Functions
Apx.
Example
Connection
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions
12.4 Positioning Using Batch Setting Method
12 Examples of Programs
3 Click on the «Positioning» tab, and then set Y000 (pulse output destination)
as follows.
Before clicking on the "Positioning" tab, click on the «Memory Capacity» tab, and then enter a check in the
"Positioning Instruction Settings" check box. After entering a check, positioning data can be set.
*1. Only available for FX
3U and FX3UC PLCs.
4 Click on the "Individual setting" button. The "Positioning Instruction
Settings" screen will appear. In this screen, click on the «Y0» tab to display
the positioning table for Y000 (pulse output destination). Set the data in the
positioning table as follows:
Setting item Setting value
Bias Speed [Hz] 500
Max. Speed [Hz] 100,000
Creep Speed [Hz] 1000
Zero Return Speed [Hz] 50,000
Acceleration Time [ms] 100
Deceleration Time [ms] 100
Interrupt Input for DVIT Instruction
*1
X000
Setting item Setting value
Rotation Direction Signal Y004
Head Address R0
No. 1
Positioning Instruction
DDRVI
(drive to increment)
Pulse (Pls) 999,999
Frequency (Hz) 30,000
No. 2
Positioning Instruction
DDRVI
(drive to increment)
Pulse (Pls) -999,999
Frequency (Hz) 30,000
No. 3
Positioning Instruction
DDRVA
(drive to absolute)
Pulse (Pls) 500,000
Frequency (Hz) 100,000
No. 4
Positioning Instruction
DDRVA
(drive to absolute)
Pulse (Pls) 100
Frequency (Hz) 100,000