4 - 16
CPU MODULE4.
List of parameter setting range (continued)
Item Default Value
Setting Range
Q02CPU-A, Q02HCPU-A Q06HCPU-A
Timer settings
T0 to T255
T0 to T199
(100ms)
T200 to
T255(10ms)
• 256 points by 100ms, 10ms, and retentive timers (in 8-point units, in 16-point units only for
1ms)
• All timers are serial numbered.
T256 to T2047 –
• 1792 points by 100ms, 10ms, and retentive timers (in 16-point units)
• All timers are serial numbered.
• Devices set: D, R, W (Setting required if 257 points or more.)
Counter setting
Interrupt counter
setting
– • Sets whether to use interrupt counter (C224 to C225) or not.
Points used
256 points (C0
to C255)
• 0 to 1024 points (in 16-point units)
• Devices set: D, R, W (Setting required if 257 points or more.)
I/O number assignment –
• 0 to 64 points (in 16-point units) .................... Input module/output module
special function module/empty slot
• Module model name can be registered.
Remote RUN/PAUSE contact setting –
• X0 to X1FFF
• RUN/PAUSE.....1 point (PAUSE contact setting is not only allowed.)
Operation mode
when there is an
error
Fuse blown Continue
Stop/Continue
I/O verify error Stop
Operation error Continue
Special function
module check error
Stop
Data communication request batch
processing
None Yes/No
Output mode switching at
STOP RUN
Set the output
status at STOP
to RUN
Output before STOP/after operation
Print title entry – • 128 characters
Keyword registration – • Up to 6 characters in hexadecimal (0 to 9, A to F)
MELSECNET/
10 link range
setting
Number of link
stations
–
Optical link.........Max. 64 stations
Coaxial link........Max. 32 stations
I/O (X/Y) X/Y0 to X/Y1FFF (in 16-point unit)
Link relay (B) B0 to B1FFF (in 16-point unit)
Link register (W) W0 to W1FFF (in 1-point unit)
Link range
settings for
MELSECNET II
Number of link
stations
–
• 0 to 64 station(s)
I/O (X/Y) X/Y0 to X/Y7FF (in 16-point units)
Link relay (B) • B0 to BFFF (in 16-point units)
Link register (W) • W0 to WFFF (in 1-point unit)