3 Replacement from FX3G to FX5UJ
3.3 Selection of Substitute Models
•FX5UJ
Cable sizes for European type terminal block
Suitable wiring and tightening torque are described below.
Differences and precautions regarding installing the FX3G and FX5UJ
The pitch of the holes for installation in a control panel differs between the FX3G and FX5UJ. When making a direct
installation in a control panel, installation holes must be added. Also, because the terminal block shapes differ, one terminal
block cannot be replaced with the other. ( Page 39 External dimension drawing)
Differences and precautions regarding the drive power supply of the output section of the
FX3G and FX5UJ
Output section power supply voltage consolidation
When replacing the FX3G with the FX5UJ, the power supplies must be consolidated if a separate power supply has been
installed with one output common terminal of the FX3G.
Maximum output load current
When the FX3G is replaced with the FX5UJ, the maximum load current of part of the output section changes.
For Y0 to Y2 on the FX3G-24M, one common terminal is used per output, but this changes to one common terminal for
three outputs in the case of Y0 to Y2 on the FX5UJ-24M.
If separate power supplies have been installed with each common terminal, consolidate the power supplies.
External color: Munsell 0.6B7.6/0.2
Unit: mm
The terminal block uses M3 terminal screws
35 mm width DIN rail can be installed
Model name W: mm W1: mm Weight: kg
FX5UJ-24M 95 76 Approx. 0.55
FX5UJ-40M 130 111 Approx. 0.65
FX5UJ-60M 175 156 Approx. 0.80
Wire size for
one wire
Wire size for
two wires
Wire ferrule with
insulation sleeve
(wire size)
Tightening
torque
Stripping dimensions of
electric wire ends
FX3G-485-BD, FX3U-485ADP(-MB) AWG22 to
AWG20
AWG22 AWG22 to AWG20 0.22 to 0.25
Nm
9 mm
FX5-485-BD, FX5-485ADP
FX5-4AD-ADP, FX5-4DA-ADP, FX5-
4A-ADP, FX5-4AD-PT-ADP, FX5-
4AD-TC-ADP
0.20 Nm
(Example) FX3G-24MT/ES (output side) (Example) FX5UJ-24MT/ES (output side)
<Maximum output load current>
Maximum load (resistance load) current of 1 output common
terminal: 0.5 A or less
<Maximum output load current>
Maximum load (resistance load) current of 1 output common terminal:
0.5 A or less
Maximum load (resistance load) current of 3 output common terminal:
0.6 A or less
Maximum load (resistance load) current of 4 output common terminal:
0.8 A or less
15
82 (mounting hole pitch)
90
W
83
8
2-
φ
4.5-diam mounting hole
W1 (mounting hole pitch)
Y2Y00V
24V
Y1
COM
1
COM2COM0 COM3
Y3
COM4
Y5 Y6
Y7 Y11
Y10
Y4
Y3Y0 Y2
Y1
COM1COM0
0V
24V Y4
Y5
COM2
Y10Y6
Y11Y7