3 DETAILS OF FUNCTION
3.1 C Intelligent Function Module Dedicated Functions
69
3
CITL_Y_In_Bit
This function reads an output signal (Y) in bit (1-point) units.
Format
short CITL_Y_In_Bit (unsigned short usYNo, unsigned short* pusData)
Argument
Description
This function reads an output signal (Y) specified to the output signal (usYNo) in bit (1-point) units.
A value of a read output signal (Y) is stored in the data storage destination (pusData).
Return value
Relevant function
Page 65 CITL_X_In_Bit
Page 66 CITL_X_In_Word
Page 67 CITL_X_Out_Bit
Page 68 CITL_X_Out_Word
Page 70 CITL_Y_In_Word
Argument Name Description IN/OUT
usYNo Output signal Specify the output signal (Y). (0 to 31) IN
pusData Data storage destination Specify the storage destination of read data.
The following values are stored depending on the value of an output signal
(Y).
0: OFF
1: ON
OUT
Return value Description
0 (0000H) Normal
Other than 0 (0000H) Error
For details on the error, refer to the following chapter.