4 ERROR CODE LIST
4.2 C Intelligent Function Module Dedicated Functions
111
4
4.2 C Intelligent Function Module Dedicated
Functions
The following table shows the error codes of the C intelligent function module dedicated functions.
Error code Description Corrective action
Decimal Hexadec
imal
-203 FF35H I/O signal error
The specified I/O signal is out of range.
Check the specified I/O signal.
-204 FF34H I/O access size error
The specified access size of I/O signal is out of range.
Check the specified access size of I/O signal (I/O number and
read/write size in words).
-208 FF30H Offset error
The specified offset is out of range.
An AnS series module (buffer memory) has been accessed.
Check the specified offset.
Check the specified I/O number.
-209 FF2FH Buffer memory size error
The specified offset and its size is out of range.
The address of data storage buffer pointer is 0.
The specified size is 0.
Check the specified buffer memory size.
Check the offset and its size.
Check the specified data storage buffer pointer.
-210 FF2EH Read area size error
The read area size is smaller than the read size.
Check the read size.
Check the read area size.
-211 FF2DH Time setting error
The specified time is out of range.
Check the specified time.
-220 FF24H WDT type error
The specified WDT type is out of range.
Check the specified WDT type.
-224 FF20H LED setting value error
The specified LED setting value is out of range.
Check the specified LED setting value.
-225 FF1FH Event number specification error
The specified event number is out of range or duplicated.
Check the specified event number.
-231 FF19H Event timeout error
A timeout occurred while waiting for an event.
Increase the timeout time.
Check if the interrupt event number (interrupt pointer number)
is set correctly.
-234 FF16H Event wait error
An error other than timeout occurred while the function waits for
the event.
Check if a program is forcibly being terminated.
Check if the C intelligent function module is running normally.
Reset the CPU module, or turn the power OFF and ON to
reset the C intelligent function module.
-235 FF15H Number of event settings specification error
The specified number of event settings is out of range.
Check the number of specified event settings.
-237 FF13H Detailed information character string specification error
The length of the specified character string was out of range or
characters which cannot be specified was specified.
Correct the length of the specified character string or character
string data.
Application code specification error
Five or more digits of the hexadecimal number was specified for
the application code.
Change the specified application code.
-239 FF11H Memory card mounting error
Either of the following functions executed with no specified
memory card inserted.
CITL_MountMemoryCard
CITL_UnmountMemoryCard
Check if a memory card is inserted.
-240 FF10H Clock data incorrect error
The clock data to be set or the read clock data is incorrect.
Check the clock data to be set.
If this error occurs when reading the clock data, set the data
again.
-241 FF0FH Cycle specification error
The specified cycle is out of range.
The cycle was set even when it had already been set.
Check the specified cycle.
Check if the cycle has been already set.
-242 FF0EH Synchronization type specification error
The specified synchronization type is out of range.
Check the specified synchronization type.
-246 FF0AH Timer event registration error
Registering a timer event failed.
•Retry.
Check if the C intelligent function module is running normally.
Reset the CPU module, or turn the power OFF and ON to
reset the C intelligent function module.
-257 FEFFH Interrupt event type specification error
The value specified to the interrupt event type is out of range.
Check the specified value.