80
3 DETAILS OF FUNCTION
3.1 C Intelligent Function Module Dedicated Functions
CITL_X_Out_Word_ISR
This function writes to an input signal (X) in word (16-point) units.
Format
short CITL_X_Out_Word_ISR (unsigned short usXNo, unsigned short usSize, unsigned short* pusDataBuf)
Argument
Description
This function writes to the input signal (X) with a specific write data size (usSize) from the start input signal (usXNo)
depending on the data storage destination (pusDataBuf). (Turns ON/OFF.)
Only the area available for user can be written. Even though the data is written by the CITL_X_Out_Word function in the
area other than the area available for user, no error will occur, but the value will not be written.
Store write data in the data storage destination (pusDataBuf) in ascending order from the lower bit.
Do not execute CITL_X_Out_Word_ISR function in a routine other than the one registered in the interrupt.
WARNING
CITL_X_Out_Word_ISR function does not check the specified argument.
Create a program with the following conditions in mind.
The input signal (X) within the range (0H to 1FH) is specified.
Return value
Relevant function
Page 79 CITL_X_In_Word_ISR
Page 81 CITL_Y_In_Word_ISR
Argument Name Description IN/OUT
usXNo Start input signal Specify a start input signal (X).
(Only 0x00 and 0x10 can be specified.)
IN
usSize Write data size Specify the write data size in word units.
When start input signal is 0x00: Only 1 and 2 can be specified.
When start input signal is 0x10: Only 1 can be specified.
IN
pusDataBuf Data storage destination Specify the storage destination of write data. IN
Storage position Description
pusDataBuf[0] Data of usXNo+FH to usXNo
pusDataBuf[1] Data of usXNo+1FH to usXNo+10H
Return value Description
0 (0000H) Normal
Other than 0 (0000H) Error
For details on the error, refer to the following chapter.
Page 108 ERROR CODE LIST