130
6 INSTALLATION AND WIRING
6.6 Wiring of Connector for Module Power Supply and FG
4. Crimping
Hold the center of plug cover with pliers and squeeze the
cover in.
Fully push in the both edges (parts holding latches) of the
plug cover. Check that the latches are engaged with the plug
body.
Side view
[Correct crimping] 5. Checking the crimped state (from the wire side)
Check that the plug body and plug cover are aligned
horizontally seen from the wire side.
The lifted part of the plug cover must be 0.2mm or less.
As shown in the incorrect crimping, if the plug cover is lifted
aslant or protruded from the plug body by more than 0.2mm,
it may result in improper crimping.
Push in the plug cover correctly and fully with pliers as shown
in the correct crimping.
[Incorrect crimping]
[Correct crimping]
6. Checking the crimped state (from the above)
Check that there is no clearance between the plug body and
plug cover seen from the above.
As shown in the incorrect crimping, latches engaged
improperly cause clearance between the plug body and plug
cover.
Push in the plug cover correctly and fully with pliers as shown
in the correct crimping.
[Incorrect crimping]
Pliers
Latches
Pliers
0.2mm or less
Latches
Clearance
Latch