How to resolve Conversion speed setting out-of-range on Mitsubishi Electric NZ2EX2B-60AD4 Controller?
- DDr. Nancy CalhounSep 5, 2025
To correct a 'Conversion speed setting out-of-range' error on your Mitsubishi Electric Controller, set the Conversion speed setting (address: 0001H) to one of the following values: 400µs/channel (0H), 1ms/channel (1H), or 100µs/channel (2H).