198
Appendix 1.2 Remote output signals
(1) Initial data setting request flag
Turn on Initial data setting request flag (RY9) after writing parameter data to the remote buffer memory.
Upon completion of the change of operating conditions, Initial data setting completed flag (RX9) turns on.
For the timing "OFFONOFF", refer to the following:
Initial data setting completed flag ( Page 190, Appendix 1.1 (2))
(a) Device number
The device number of this output signal is as follows:
(2) Error clear request flag
This signal is used for clearing Error flag (RXA), Input signal error detection signal (RX1C, RX2C), and Latest
error code (RWr0).
(a) When a moderate error or input signal error detection occurs
Eliminating the cause of the error and turning on Error clear request flag (RYA) from off allows the error status
to be cleared, resulting in Error flag (RXA) turning off.
Before Error flag (RXA) turns off, turning off Error clear request flag (RYA) from on does not allow Error flag
(RXA) to turn off.
For the timing "OFFONOFF", refer to the following:
Error flag ( Page 191, Appendix 1.1 (3))
Input signal error detection signal ( Page 195, Appendix 1.1 (9))
(b) When a major error occurs
Error flag (RXA) does not turn off even by turning on and off Error clear request flag (RYA).
For the timing "OFFONOFF", refer to the following:
Error flag ( Page 191, Appendix 1.1 (3))
(c) Device number
The device number of this output signal is as follows:
Signal name Main A/D converter module Extension A/D converter module
Initial data setting request flag RY9
Signal name Main A/D converter module Extension A/D converter module
Error clear request flag RYA