Appendix 1 Details of Remote I/O Signals
Appendix 1.1 Remote input signals
(3) Error flag
In the event of a moderate error or a major error, Error flag (RXA) turns on.
To clear Latest error code (RWr0), turn on and off Error clear request flag (RYA).
With a moderate error
With a major error
(a) Error history
The error history is not cleared even if Error clear request flag (RYA) is turned on and off. To clear the error
history, set "1" in Error history clear command (address: 1000H).
For the error history clear, refer to the following:
Error history clear command ( Page 223, Appendix 3 (24))
(b) Device number
The device number of this input signal is as follows:
Signal name Main A/D converter module Extension A/D converter module
Error flag RXA
Error flag (RXA)
Latest error code (RWr0)
Error occurred
(Error code)0000H 0000H
ON
OFF
OFF
OFF
ON
Error clear request flag
(RYA)
Remote READY (RXB)
Controlled by the A/D converter module
Controlled by the program
ON
ON
ON
Controlled by the program
Controlled by the A/D converter module
Remote READY (RXB)
Error clear request flag
(RYA)
In the case of a major error, the error is not
cleared by an error clear request.
ON
OFF
OFF
ON
0000H (Error code)
Error occurred
Latest error code (RWr0)
Error flag (RXA)