CHAPTER 6 INSTALLATION AND WIRING
6
6.6 Wiring of Terminal Block and External Devices
6.6 Wiring of Terminal Block and External Devices
(1) Tightening torque
Tighten the terminal block screws within the following specified torque range.
Tightening the screws too much may damage the module case.
The following table shows applicable solderless terminals to be connected to the terminal block. For wiring, use
the wire and tightening torque as specified in the table below. Use UL-listed solderless terminals, and for
processing, use the tool recommended by their manufacturers. Note that a solderless terminal with an insulation
sleeve cannot be used.
Screw type Tightening torque range
Terminal screw (M3) 0.43 to 0.57Nm
Terminal block mounting screw (M3.5) 0.68 to 0.92Nm
Solderless terminal Wire
Model Applicable tightening torque Diameter Type Material Temperature rating
R1.25-3
0.43 to 0.57Nm 22 to 14 AWG Stranded Copper 75 or higher
V2-MS3
RAP2-3SL
TGV2-3N