80
7.2.2 Changing the parameters without changing the network
configuration
To change only the module parameters of the already set-up slave station without changing the network configuration,
take the following steps:
1. Open the "CC IE Field Configuration" window.
For the master/local module QJ71GF11-T2
Project window [Parameter] [Network Parameter]
[Ethernet/CC IE/MELSECNET] button
For the master/local module LJ71GF11-T2
Project window [Parameter] [Network Parameter]
[Ethernet/CC IE Field] button
2. On the "CC IE Field Configuration" window, from "List of stations", select the A/D converter
module.
3. Open the "Parameter Processing of Slave Station" window.
[CC IE Field Configuration] [Online] [Parameter Processing of Slave Station]
4. Set "Method selection" to "Parameter read".