CHAPTER 7 VARIOUS SETTINGS
7
7.1 Parameter Settings
CHAPTER 7 VARIOUS SETTINGS
This chapter describes how to set up various settings of the A/D converter module.
7.1 Parameter Settings
Set the parameter of this module with the network parameter written to the CPU module of the master station. For the
setting procedure of the master station, refer to the following:
User's manual for the master/local module used
● Place a checkmark in the "Set the network configuration settings in CC IE Field configuration window" box on the
"MELSECNET/CC IE/Ethernet Module Configuration" window in advance.
● To select the main A/D converter module in the CC IE Field Configuration window, select "NZ2GF2B-60AD4" from the
"Module List" window.
● To select an extension module in the "CC IE Field Configuration" window, select the following models from the "Module
List" window.
● Setting fewer points of the remote I/O signal or remote register than actual points that the main A/D converter module or
the extension module possesses does not cause an error. In this case, data of all the set points are subject to cyclic
transmission in order.
Extension module type Name
Extension Digital Input Module NZ2EX-16 (DI)
Extension Digital Output Module NZ2EX-16 (DO)
Extension A/D Converter Module NZ2EX2B-60AD4
Extension D/A Converter Module NZ2EX2B-60DA4